  • Floor plan design requirements

    • 1. Each passageway in the exhibition area must not be less than 4m. The main passageways in exhibition halls 1 to 6 shall be wider than 6m; and the main passageway for the metro exhibition hall shall be wider than 5m.
    • 2. No booth shall be built under the fire shutters, and the fire doors shall not be blocked. At least 4m shall be reserved in front of the safety exit. A 4m-wide fire escape exit shall be reserved for continuous single-row booths in every 25m.
    • 3. For booths against the wall, there shall be a 1m-wide working passageway between the backboard and the wall to ensure fire hydrant and equipment room door can be opened properly.
  • Fire safety rules

    • 1. To ensure fire safety and the comfort of the exhibition environment, no smoking is allowed in the Expo area, including all exhibition halls, public areas, stairwells, restrooms and food courts.
    • 2. Non-combustible or flame retardant materials should be used for special booth construction. It is strictly forbidden to use the ordinary splint or the splint coated with fire-retardant paint for special decorations. The venue security department will check when the construction materials move into the scene. For construction unit that uses fake fireproof materials for decoration, the Expo reserves the final right to refuse its entry. "One-vote veto" system is implemented for fire safety.
    • 3. No materials without fire retardant treatment such as grass, bamboo, rattan, paper, bark, reed, carpet, cloth and wood board shall be used in the exhibition hall for decoration.
    • 4. Welding and open fire operations are prohibited in the exhibition hall. Exhibitors and special contractors shall not use cutting machines or chainsaws, or hand-painting on site.
    • 5. All booths and decoration should not be capped to ensure normal operation of the automatic fire alarm system and automatic sprinkler system. For capped booth, a 6kg hanged dry powder extinguisher shall be installed in every 20m2.
    • 6. If the organizer (co-organizer) needs to exhibit or bring controlled, dangerous, prohibited or harmful products or animals into the exhibition hall, it must be approved by the relevant government authorities and obtain special permit; and at the same time, written consent from relevant departments of the venue.
    • 7. No booth shall be built under the fire shutters, and the fire doors shall not be blocked. At least 3m shall be reserved in front of the safety exit. A 3m-wide fire escape shall be reserve in every 25m for continuous single-row booths.
  • Booth erection rules

    • 1. Erection of special booths shall be undertaken by contractors with corresponding special booth construction and exhibition qualifications. Exhibitors shall not carry out the construction of special booths by themselves.
    • 2. All structures of the special booths shall be pre-made into semi-finished products outside the venue. It is strictly forbidden to carry out large-scale ash brushing and painting indoors. During the exhibition period, small scale "repairing" painting of construction materials and exhibits can be carried out, provided that necessary safety precautions must be taken.
    • 3. The vertical projection of the booth must not exceed the range of reserved space. If the same exhibiting company uses multiple booths, and all the booths have public passages in the middle, they must not cross the passage or build a second-floor aisle during design.
    • 4. The booth design should adopt a simple structure and use environmentally friendly materials that can be used repeatedly. The side wall of each booth passageway shall be made of translucent material or window, rather than a fully enclosed wall. If the booth is in the form of full enclosure, the main passage with a straight line distance of more than 15m must be opened to ensure fire safety.
    • 5. The height of all booths must not exceed 6m (the ground floor and the corridor exhibition area must not exceed 3m). In addition to the basement exhibition area, double-decker is allowed for booth larger than 90m2. The construction area of the second floor booth is limited to 30% of the area of the first floor booth, and the design height must follow the regulations specified by the operator.
    • 6. The load-bearing structure of a double-decker must be calculated and verified by qualified design units. The bearing capacity of the second floor booth should be in the range of 500 to 400 kg/m2. The second floor booth is limited to negotiation or rest. The main purpose of placing exhibits is to strictly control the number of people staying in the second floor booth.
    • 7. The second floor booth should be covered by lightweight materials and semi-transparent design (or window design) to ensure the air quality in the booth. The handrail of the booth shall not be lower than 1.5 meters. The handrail surface of the railing should be curved to prevent the misplaced items from slipping off the railing.
    • 8. For erection of a double-decker, the first floor must have its own 6kg automatic spray dry powder fire extinguisher, one for every 20m2. In the booth above the door and on the second floor stairway, a luminous "safe exit" evacuation sign must be installed and sufficient emergency lighting fixtures should be installed in the booth. When constructing a double-decker with an upper floor area of more than 100m2, at least two stairway evacuation openings must be provided.
  • Power supply service rules

    • 1. The power supply standard of the Expo is TN-S system, 50 Hz.
    • 2. For standard booths, the exhibitors are not allowed to use their own lamps. There shall not be any high-power electric equipment such as electric kettles, electric irons, induction cookers, etc. If you really need to use such devices, please apply for a separate electricity boxes.
    • 3. If the special booth erection involves electrical installation, the construction unit must have electrical installation qualification. The electrician must hold a valid operation certificate issued by the National Technical Supervision Department, and apply for the certificate registration at the construction permit handling point with the above-mentioned valid certificate. The electrician must carry valid operation certificate to do the job, otherwise he/she is not allowed to enter the construction.
    • 4. Special contractors engaged by exhibitors must follow the "Regulations on Electrical Equipment Installations in Guangzhou". The selected electrical materials and facilities must comply with the National Compulsory Product Certification (3C) standards and fire safety requirements. The safe and reliable air circuit breaker and 30MA (operating time less than 0.1S) leakage protector must be set in the booth distribution switch box. The wire shall be ZR-BVV (resistance to flame retardant double-plastic copper core wire) and sheathed wire that have been inspected by the public security fire department. Stranded wire (electric cord) and aluminum core wire are prohibited.
    • 5. For circuit design, the single-phase loop must not exceed 1000W. If it exceeds 1000W, the three-phase power supply design shall be adopted to balance the distribution of power load. Each electrical circuit must have a dedicated protective ground wire (using a copper wire of not less than 2.5mm2) and connected to any metal object that may be in contact with the leakage.
    • 6. Lighting and mechanical power should be connected separately. Sub-switch graded protection shall be adopted for non-mechanical power with a three-phase load exceeding 20A. For single-phase loads exceeding 16A, a three-phase power supply design should be used, and the booth's load shall be evenly distributed among the three phases. The protection setting value of the main switch of the booth shall be lower than or equal to 80% of the protection setting value of the fixed power box of the exhibition hall.
    • 7. Various lighting fixtures shall be at least 30cm away from the exhibits. Down lights and quartz lamps shall be insulated and protected; convection holes shall be set in the billboards, light boxes and lamp posts. Lamp ballasts and triggers shall be qualified products inspected by the fire department. Protective covers shall be installed outside the high-power heating lamps (such as 100W iodine tungsten lamp) on a non-combustible structure. It is forbidden to use high-power lamps of 500W or more.
    • 8. Electrical wires passing through the pedestrian floor and carpet, and those laying in the decorative structures concealed must be protected by pipes (metal pipes, flame retardant plastic pipes). Metal protection tubes and metal components must be reliably electrically bridged and safely grounded.
    • 9. During the erection and exhibition periods, the organizer (co-organizer) and exhibitors must apply to the main contractor for extra electricity use. No private connection is allowed, otherwise the relevant unit or personnel will be dealt with accordingly.
    • 10. After all the electrical equipment of the booth has been installed, it is not allowed to close the switch before the electrician of the exhibition inspect and agree the switching in and power transmission. The main load switch should be in the disconnected position. Switching in and power transmission is only allowed after the inspection and acceptance by the exhibition hall electrician.
  • Vehicle use rules

    The trucks will arrive at the entrance of the unloading area located in the southwest of the exhibition hall. The special design vehicles and exhibit vehicles shall enter the venue with "move-in/move-out pass" and organizer-issued exhibit vehicle certificate respectively and shall comply with the following regulations:

    • 1. The drivers shall carry valid vehicle licenses, and handle the entrance procedures at the entrance of the exhibition hall. A 200 Yuan/time/vehicle of move-in deposit will be charged;
    • 2. One move-in/move-out pass corresponds to one vehicle. No alteration, under-lease or other action that violates the order of the hall is allowed.
    • 3. The entry of move-in/move-out vehicle must operate in accordance with the "certificate time", a 500 Yuan/time/vehicle fine will be imposed for vehicles arrive earlier but not follow instructions;
    • 4. For vehicles in the unloading area, if the move-in/move-out pass is not placed at the front windshield, the on-site management personnel can treat such vehicles as no-pass vehicles and shall have the right to imposes a fine of 200 Yuan/ vehicle;
    • 5. During the move-in/move-out period, the first unloading floor only allows vehicles with a loading capacity higher than 0.6t. Allowed staying time:
      ① Free unloading time of 2 hours for vehicles with a loading capacity of 0.6 to 4.99t with valid move-in/move-out pass;
      ② Free unloading time of 3 hours for vehicles with a loading capacity of 5t (included) with valid move-in/move-out pass;
      ③ Truck/sedan/minibus/medium bus under 0.6t (included) shall be parked at the unloading area in the ground floor of phase I project;
    • 6. The driver must not leave the vehicle after entering the location, otherwise he/she will be given a penalty of 200 Yuan;
    • 7. Vehicles entering the unloading area shall be parked in accordance with the instructions of the on-site security personnel; beware of the unloading and entering safety and prevent any accident. Damages to facilities and equipment of the exhibition hall must be compensated according to their costs. The vehicle shall not block the passageway maliciously, otherwise a 1,000 Yuan penalty will be deducted from the construction deposit;
    • 8. In special cases (exhibit vehicle/forklift/crane/large machinery need to enter the venue), the user shall apply to the organizer and only enters the venue upon approval by the venue operation manager;
    • 9. When moving out, the deposit receipt must carry the move-out time of the vehicle specified by the Security Department. The deposit shall be refunded on the same day as the payment, i.e. the date must be consistent with the date on the deposit receipt. For instance: if the deposit receipt specifies 8am on March 23rd, then the deposit refund must be done before 23:59 on March 23rd.
    • 10. If there's any over time, a 50 Yuan/hour parking fee will be deducted from deposit and the remainder will be refunded.